18 seer trane works in A.C. goes off on high head pressure in heat after 1 min

by Richard
(Chesterfield, VA)



I have replaced the out door eev and the reversing valve. I have also replaced the eev stepper control and the temp sensor for the eev and sensor on the high side in the unit by the high pressure sensor I for got the name of... I have replaced the eev control board too.
I weighed in the r-410 a so I know the unit is not over charged.
This trane unit runs for 1 - 1min 30sec in heat mode the cuts off at 650psi on the liquid line high pressure in heat mode. In a\c mode I have normal pressures and it runs normal. This system is duel fuel attached to a coil and a gas furnace.

Comments for 18 seer trane works in A.C. goes off on high head pressure in heat after 1 min

Average Rating starstarstarstarstar

Click here to add your own comments

Jan 26, 2018
Rating
starstarstarstarstar
had same issue NEW
by: Anonymous

mismatched indoor coil

Jan 26, 2018
Rating
starstarstarstar
had same issue NEW
by: Earl,Henrico

mismatched indoor coil is what it turned out to be although Trane was the one who matched them

Click here to add your own comments

Join in and write your own page! It's easy to do. How? Simply click here to return to Heat Pump Problems.