Even though temp is met on thermostat and inside unit shuts off the condensing fan outside continues to run and will not shut off

Comments for Goodman heat pump condensing fan

Average Rating starstarstarstarstar

Click here to add your own comments

Nov 09, 2015
Rating
starstarstarstarstar
fan stuck on because of melted board
by: Anonymous

Mine had the same problem. The circuit board had malfunctioned and overheated and caused the fan to stay on all the time. You can see the burnt connections when you take the top cover off.

Oct 24, 2014
Rating
starstarstarstarstar
Stuck Contactor
by: Ex-HVAC Instructor

If the outdoor fan is running the compressor is also running, probably due to stuck contacts in the contactor. This happens sometimes when the contacts are badly worn.