Heats above set temperature

by Gary
(Prosser,Wash,99350)

Lennox HP32 Unit. Experiencing heating problems. Unit continues to heat above temperature setting on thermostat. When shutting unit off pump will continue to run more than a few min's. So I switch off unit at breaker panel. I'll wait about an hr.when temp drops to 69 degrees and restart with thermostat set @ 70 degrees. The same problem will occur again. ?????? This unit is 10 yrs old.

Comments for Heats above set temperature

Average Rating starstarstarstarstar

Click here to add your own comments

Oct 20, 2015
Rating
starstarstarstarstar
Article
by: Anonymous

Good!

Oct 24, 2014
Rating
starstarstarstarstar
Thermostat?
by: Ex-HVAC Instructor

May be a bad thermostat. If the room temp goes above the thermostat set point it is almost certain to be a thermostat problem. If you remove the thermostat, then use a jumper wire from the Red to Yellow wires, outdoor unit should run, remove jumper, outdoor unit should stop. Turn off circuit breakers for indoor and outdoor units before removing or installing thermostat, turn breakers on for testing. Failure to do this may blow a low voltage fuse or transformer.

Apr 07, 2014
Rating
starstarstarstarstar
check these first
by: Mark

Check the T-stat setting and try adjusting the degree tolerance on the Stat. The other issue sounds
like the DFC Board. 1 or the other.